Systemair BKF 315D4-6-XL/F400
Модель: BKF
Артикул: 95689
Dual purpose fans: normal ventilation plus smoke and heat extract
• 400°C/120 min (F400)• Continuous operation up to 120°C media
• Casing made of zinc-magnesium coated steel (ZM)
• Backward curved impeller made from pre-galvanized steel or from steel and galvanized
• Motor outside the air stream
• Single speed IE2 motors (IE1 exceptions at some items up to 0,55 kW and 8 pole) rsp. two speed motors
• PTC serial built-in motor
• Certified according EN 12101-3 by BSI
• Installation possible in all positions, flange connection 30 mm
• Installation outside building or inside building, outside fire zone in well ventilated rooms
BKF smoke and heat extract fans are used in case of fire to extract smoke gases and also during normal working conditions for standard ventilation.
Smoke free escape routes assist egress and provide clear access points for fire departments. Extracting poisonous and hot gases also make fire extinguishing easier and reduce the damage on the building.
Applications: malls, garages, warehouses, kitchen exhaust...
Generally suitable for ambient temperature -20 to +40°C (depending on specific motor load the permissible ambient temperature may be increased - on request)
For speed control of single speed motors use combination of frequency converter and appropriate filter to motor side (sine or du/dt), respectively observe instructions. Not suitable for voltage control. Working points within blue area of diagrams of single speed fans can be achieved with frequency converter. Tested to 400°C/2h together with frequency converter. However, we recommend bridging of frequency converter in case of fire to eliminate possible risk of malfunction of frequency converter. In case of fire all motor protective devices and thermal protections in frequency converter must be bridged or disabled to guarantee functional capability. When choosing AES control accessory please observe serial connecting capability of the motor (instructions).
Systemair BKF 315D4-8-XL/F400
Модель: BKF
Артикул: 95690
Dual purpose fans: normal ventilation plus smoke and heat extract
• 400°C/120 min (F400)• Continuous operation up to 120°C media
• Casing made of zinc-magnesium coated steel (ZM)
• Backward curved impeller made from pre-galvanized steel or from steel and galvanized
• Motor outside the air stream
• Single speed IE2 motors (IE1 exceptions at some items up to 0,55 kW and 8 pole) rsp. two speed motors
• PTC serial built-in motor
• Certified according EN 12101-3 by BSI
• Installation possible in all positions, flange connection 30 mm
• Installation outside building or inside building, outside fire zone in well ventilated rooms
BKF smoke and heat extract fans are used in case of fire to extract smoke gases and also during normal working conditions for standard ventilation.
Smoke free escape routes assist egress and provide clear access points for fire departments. Extracting poisonous and hot gases also make fire extinguishing easier and reduce the damage on the building.
Applications: malls, garages, warehouses, kitchen exhaust...
Generally suitable for ambient temperature -20 to +40°C (depending on specific motor load the permissible ambient temperature may be increased - on request)
For speed control of single speed motors use combination of frequency converter and appropriate filter to motor side (sine or du/dt), respectively observe instructions. Not suitable for voltage control. Working points within blue area of diagrams of single speed fans can be achieved with frequency converter. Tested to 400°C/2h together with frequency converter. However, we recommend bridging of frequency converter in case of fire to eliminate possible risk of malfunction of frequency converter. In case of fire all motor protective devices and thermal protections in frequency converter must be bridged or disabled to guarantee functional capability. When choosing AES control accessory please observe serial connecting capability of the motor (instructions).
Systemair BKF 355D4-6/F400
Модель: BKF
Артикул: 95693
Dual purpose fans: normal ventilation plus smoke and heat extract
• 400°C/120 min (F400)• Continuous operation up to 120°C media
• Casing made of zinc-magnesium coated steel (ZM)
• Backward curved impeller made from pre-galvanized steel or from steel and galvanized
• Motor outside the air stream
• Single speed IE2 motors (IE1 exceptions at some items up to 0,55 kW and 8 pole) rsp. two speed motors
• PTC serial built-in motor
• Certified according EN 12101-3 by BSI
• Installation possible in all positions, flange connection 30 mm
• Installation outside building or inside building, outside fire zone in well ventilated rooms
BKF smoke and heat extract fans are used in case of fire to extract smoke gases and also during normal working conditions for standard ventilation.
Smoke free escape routes assist egress and provide clear access points for fire departments. Extracting poisonous and hot gases also make fire extinguishing easier and reduce the damage on the building.
Applications: malls, garages, warehouses, kitchen exhaust...
Generally suitable for ambient temperature -20 to +40°C (depending on specific motor load the permissible ambient temperature may be increased - on request)
For speed control of single speed motors use combination of frequency converter and appropriate filter to motor side (sine or du/dt), respectively observe instructions. Not suitable for voltage control. Working points within blue area of diagrams of single speed fans can be achieved with frequency converter. Tested to 400°C/2h together with frequency converter. However, we recommend bridging of frequency converter in case of fire to eliminate possible risk of malfunction of frequency converter. In case of fire all motor protective devices and thermal protections in frequency converter must be bridged or disabled to guarantee functional capability. When choosing AES control accessory please observe serial connecting capability of the motor (instructions).
Systemair BKF 355D4-8/F400
Модель: BKF
Артикул: 95694
Dual purpose fans: normal ventilation plus smoke and heat extract
• 400°C/120 min (F400)• Continuous operation up to 120°C media
• Casing made of zinc-magnesium coated steel (ZM)
• Backward curved impeller made from pre-galvanized steel or from steel and galvanized
• Motor outside the air stream
• Single speed IE2 motors (IE1 exceptions at some items up to 0,55 kW and 8 pole) rsp. two speed motors
• PTC serial built-in motor
• Certified according EN 12101-3 by BSI
• Installation possible in all positions, flange connection 30 mm
• Installation outside building or inside building, outside fire zone in well ventilated rooms
BKF smoke and heat extract fans are used in case of fire to extract smoke gases and also during normal working conditions for standard ventilation.
Smoke free escape routes assist egress and provide clear access points for fire departments. Extracting poisonous and hot gases also make fire extinguishing easier and reduce the damage on the building.
Applications: malls, garages, warehouses, kitchen exhaust...
Generally suitable for ambient temperature -20 to +40°C (depending on specific motor load the permissible ambient temperature may be increased - on request)
For speed control of single speed motors use combination of frequency converter and appropriate filter to motor side (sine or du/dt), respectively observe instructions. Not suitable for voltage control. Working points within blue area of diagrams of single speed fans can be achieved with frequency converter. Tested to 400°C/2h together with frequency converter. However, we recommend bridging of frequency converter in case of fire to eliminate possible risk of malfunction of frequency converter. In case of fire all motor protective devices and thermal protections in frequency converter must be bridged or disabled to guarantee functional capability. When choosing AES control accessory please observe serial connecting capability of the motor (instructions).
Systemair BKF 400D4-6-XL/F400
Модель: BKF
Артикул: 95700
Dual purpose fans: normal ventilation plus smoke and heat extract
• 400°C/120 min (F400)• Continuous operation up to 120°C media
• Casing made of zinc-magnesium coated steel (ZM)
• Backward curved impeller made from pre-galvanized steel or from steel and galvanized
• Motor outside the air stream
• Single speed IE2 motors (IE1 exceptions at some items up to 0,55 kW and 8 pole) rsp. two speed motors
• PTC serial built-in motor
• Certified according EN 12101-3 by BSI
• Installation possible in all positions, flange connection 30 mm
• Installation outside building or inside building, outside fire zone in well ventilated rooms
BKF smoke and heat extract fans are used in case of fire to extract smoke gases and also during normal working conditions for standard ventilation.
Smoke free escape routes assist egress and provide clear access points for fire departments. Extracting poisonous and hot gases also make fire extinguishing easier and reduce the damage on the building.
Applications: malls, garages, warehouses, kitchen exhaust...
Generally suitable for ambient temperature -20 to +40°C (depending on specific motor load the permissible ambient temperature may be increased - on request)
For speed control of single speed motors use combination of frequency converter and appropriate filter to motor side (sine or du/dt), respectively observe instructions. Not suitable for voltage control. Working points within blue area of diagrams of single speed fans can be achieved with frequency converter. Tested to 400°C/2h together with frequency converter. However, we recommend bridging of frequency converter in case of fire to eliminate possible risk of malfunction of frequency converter. In case of fire all motor protective devices and thermal protections in frequency converter must be bridged or disabled to guarantee functional capability. When choosing AES control accessory please observe serial connecting capability of the motor (instructions).
Systemair BKF 400D4-6-XS/F400
Модель: BKF
Артикул: 95697
Dual purpose fans: normal ventilation plus smoke and heat extract
• 400°C/120 min (F400)• Continuous operation up to 120°C media
• Casing made of zinc-magnesium coated steel (ZM)
• Backward curved impeller made from pre-galvanized steel or from steel and galvanized
• Motor outside the air stream
• Single speed IE2 motors (IE1 exceptions at some items up to 0,55 kW and 8 pole) rsp. two speed motors
• PTC serial built-in motor
• Certified according EN 12101-3 by BSI
• Installation possible in all positions, flange connection 30 mm
• Installation outside building or inside building, outside fire zone in well ventilated rooms
BKF smoke and heat extract fans are used in case of fire to extract smoke gases and also during normal working conditions for standard ventilation.
Smoke free escape routes assist egress and provide clear access points for fire departments. Extracting poisonous and hot gases also make fire extinguishing easier and reduce the damage on the building.
Applications: malls, garages, warehouses, kitchen exhaust...
Generally suitable for ambient temperature -20 to +40°C (depending on specific motor load the permissible ambient temperature may be increased - on request)
For speed control of single speed motors use combination of frequency converter and appropriate filter to motor side (sine or du/dt), respectively observe instructions. Not suitable for voltage control. Working points within blue area of diagrams of single speed fans can be achieved with frequency converter. Tested to 400°C/2h together with frequency converter. However, we recommend bridging of frequency converter in case of fire to eliminate possible risk of malfunction of frequency converter. In case of fire all motor protective devices and thermal protections in frequency converter must be bridged or disabled to guarantee functional capability. When choosing AES control accessory please observe serial connecting capability of the motor (instructions).
Systemair BKF 400D4-8-XL/F400
Модель: BKF
Артикул: 95701
Dual purpose fans: normal ventilation plus smoke and heat extract
• 400°C/120 min (F400)• Continuous operation up to 120°C media
• Casing made of zinc-magnesium coated steel (ZM)
• Backward curved impeller made from pre-galvanized steel or from steel and galvanized
• Motor outside the air stream
• Single speed IE2 motors (IE1 exceptions at some items up to 0,55 kW and 8 pole) rsp. two speed motors
• PTC serial built-in motor
• Certified according EN 12101-3 by BSI
• Installation possible in all positions, flange connection 30 mm
• Installation outside building or inside building, outside fire zone in well ventilated rooms
BKF smoke and heat extract fans are used in case of fire to extract smoke gases and also during normal working conditions for standard ventilation.
Smoke free escape routes assist egress and provide clear access points for fire departments. Extracting poisonous and hot gases also make fire extinguishing easier and reduce the damage on the building.
Applications: malls, garages, warehouses, kitchen exhaust...
Generally suitable for ambient temperature -20 to +40°C (depending on specific motor load the permissible ambient temperature may be increased - on request)
For speed control of single speed motors use combination of frequency converter and appropriate filter to motor side (sine or du/dt), respectively observe instructions. Not suitable for voltage control. Working points within blue area of diagrams of single speed fans can be achieved with frequency converter. Tested to 400°C/2h together with frequency converter. However, we recommend bridging of frequency converter in case of fire to eliminate possible risk of malfunction of frequency converter. In case of fire all motor protective devices and thermal protections in frequency converter must be bridged or disabled to guarantee functional capability. When choosing AES control accessory please observe serial connecting capability of the motor (instructions).
Systemair BKF 450D4-6/F400
Модель: BKF
Артикул: 95704
Dual purpose fans: normal ventilation plus smoke and heat extract
• 400°C/120 min (F400)• Continuous operation up to 120°C media
• Casing made of zinc-magnesium coated steel (ZM)
• Backward curved impeller made from pre-galvanized steel or from steel and galvanized
• Motor outside the air stream
• Single speed IE2 motors (IE1 exceptions at some items up to 0,55 kW and 8 pole) rsp. two speed motors
• PTC serial built-in motor
• Certified according EN 12101-3 by BSI
• Installation possible in all positions, flange connection 30 mm
• Installation outside building or inside building, outside fire zone in well ventilated rooms
BKF smoke and heat extract fans are used in case of fire to extract smoke gases and also during normal working conditions for standard ventilation.
Smoke free escape routes assist egress and provide clear access points for fire departments. Extracting poisonous and hot gases also make fire extinguishing easier and reduce the damage on the building.
Applications: malls, garages, warehouses, kitchen exhaust...
Generally suitable for ambient temperature -20 to +40°C (depending on specific motor load the permissible ambient temperature may be increased - on request)
For speed control of single speed motors use combination of frequency converter and appropriate filter to motor side (sine or du/dt), respectively observe instructions. Not suitable for voltage control. Working points within blue area of diagrams of single speed fans can be achieved with frequency converter. Tested to 400°C/2h together with frequency converter. However, we recommend bridging of frequency converter in case of fire to eliminate possible risk of malfunction of frequency converter. In case of fire all motor protective devices and thermal protections in frequency converter must be bridged or disabled to guarantee functional capability. When choosing AES control accessory please observe serial connecting capability of the motor (instructions).
Systemair BKF 450D4-8/F400
Модель: BKF
Артикул: 95705
Dual purpose fans: normal ventilation plus smoke and heat extract
• 400°C/120 min (F400)• Continuous operation up to 120°C media
• Casing made of zinc-magnesium coated steel (ZM)
• Backward curved impeller made from pre-galvanized steel or from steel and galvanized
• Motor outside the air stream
• Single speed IE2 motors (IE1 exceptions at some items up to 0,55 kW and 8 pole) rsp. two speed motors
• PTC serial built-in motor
• Certified according EN 12101-3 by BSI
• Installation possible in all positions, flange connection 30 mm
• Installation outside building or inside building, outside fire zone in well ventilated rooms
BKF smoke and heat extract fans are used in case of fire to extract smoke gases and also during normal working conditions for standard ventilation.
Smoke free escape routes assist egress and provide clear access points for fire departments. Extracting poisonous and hot gases also make fire extinguishing easier and reduce the damage on the building.
Applications: malls, garages, warehouses, kitchen exhaust...
Generally suitable for ambient temperature -20 to +40°C (depending on specific motor load the permissible ambient temperature may be increased - on request)
For speed control of single speed motors use combination of frequency converter and appropriate filter to motor side (sine or du/dt), respectively observe instructions. Not suitable for voltage control. Working points within blue area of diagrams of single speed fans can be achieved with frequency converter. Tested to 400°C/2h together with frequency converter. However, we recommend bridging of frequency converter in case of fire to eliminate possible risk of malfunction of frequency converter. In case of fire all motor protective devices and thermal protections in frequency converter must be bridged or disabled to guarantee functional capability. When choosing AES control accessory please observe serial connecting capability of the motor (instructions).
Systemair BKF 500D4-6-XL/F400
Модель: BKF
Артикул: 95711
Dual purpose fans: normal ventilation plus smoke and heat extract
• 400°C/120 min (F400)• Continuous operation up to 120°C media
• Casing made of zinc-magnesium coated steel (ZM)
• Backward curved impeller made from pre-galvanized steel or from steel and galvanized
• Motor outside the air stream
• Single speed IE2 motors (IE1 exceptions at some items up to 0,55 kW and 8 pole) rsp. two speed motors
• PTC serial built-in motor
• Certified according EN 12101-3 by BSI
• Installation possible in all positions, flange connection 30 mm
• Installation outside building or inside building, outside fire zone in well ventilated rooms
BKF smoke and heat extract fans are used in case of fire to extract smoke gases and also during normal working conditions for standard ventilation.
Smoke free escape routes assist egress and provide clear access points for fire departments. Extracting poisonous and hot gases also make fire extinguishing easier and reduce the damage on the building.
Applications: malls, garages, warehouses, kitchen exhaust...
Generally suitable for ambient temperature -20 to +40°C (depending on specific motor load the permissible ambient temperature may be increased - on request)
For speed control of single speed motors use combination of frequency converter and appropriate filter to motor side (sine or du/dt), respectively observe instructions. Not suitable for voltage control. Working points within blue area of diagrams of single speed fans can be achieved with frequency converter. Tested to 400°C/2h together with frequency converter. However, we recommend bridging of frequency converter in case of fire to eliminate possible risk of malfunction of frequency converter. In case of fire all motor protective devices and thermal protections in frequency converter must be bridged or disabled to guarantee functional capability. When choosing AES control accessory please observe serial connecting capability of the motor (instructions).
Systemair BKF 500D4-6-XS/F400
Модель: BKF
Артикул: 95708
Dual purpose fans: normal ventilation plus smoke and heat extract
• 400°C/120 min (F400)• Continuous operation up to 120°C media
• Casing made of zinc-magnesium coated steel (ZM)
• Backward curved impeller made from pre-galvanized steel or from steel and galvanized
• Motor outside the air stream
• Single speed IE2 motors (IE1 exceptions at some items up to 0,55 kW and 8 pole) rsp. two speed motors
• PTC serial built-in motor
• Certified according EN 12101-3 by BSI
• Installation possible in all positions, flange connection 30 mm
• Installation outside building or inside building, outside fire zone in well ventilated rooms
BKF smoke and heat extract fans are used in case of fire to extract smoke gases and also during normal working conditions for standard ventilation.
Smoke free escape routes assist egress and provide clear access points for fire departments. Extracting poisonous and hot gases also make fire extinguishing easier and reduce the damage on the building.
Applications: malls, garages, warehouses, kitchen exhaust...
Generally suitable for ambient temperature -20 to +40°C (depending on specific motor load the permissible ambient temperature may be increased - on request)
For speed control of single speed motors use combination of frequency converter and appropriate filter to motor side (sine or du/dt), respectively observe instructions. Not suitable for voltage control. Working points within blue area of diagrams of single speed fans can be achieved with frequency converter. Tested to 400°C/2h together with frequency converter. However, we recommend bridging of frequency converter in case of fire to eliminate possible risk of malfunction of frequency converter. In case of fire all motor protective devices and thermal protections in frequency converter must be bridged or disabled to guarantee functional capability. When choosing AES control accessory please observe serial connecting capability of the motor (instructions).
Systemair BKF 500D4-8-XL/F400
Модель: BKF
Артикул: 95712
Dual purpose fans: normal ventilation plus smoke and heat extract
• 400°C/120 min (F400)• Continuous operation up to 120°C media
• Casing made of zinc-magnesium coated steel (ZM)
• Backward curved impeller made from pre-galvanized steel or from steel and galvanized
• Motor outside the air stream
• Single speed IE2 motors (IE1 exceptions at some items up to 0,55 kW and 8 pole) rsp. two speed motors
• PTC serial built-in motor
• Certified according EN 12101-3 by BSI
• Installation possible in all positions, flange connection 30 mm
• Installation outside building or inside building, outside fire zone in well ventilated rooms
BKF smoke and heat extract fans are used in case of fire to extract smoke gases and also during normal working conditions for standard ventilation.
Smoke free escape routes assist egress and provide clear access points for fire departments. Extracting poisonous and hot gases also make fire extinguishing easier and reduce the damage on the building.
Applications: malls, garages, warehouses, kitchen exhaust...
Generally suitable for ambient temperature -20 to +40°C (depending on specific motor load the permissible ambient temperature may be increased - on request)
For speed control of single speed motors use combination of frequency converter and appropriate filter to motor side (sine or du/dt), respectively observe instructions. Not suitable for voltage control. Working points within blue area of diagrams of single speed fans can be achieved with frequency converter. Tested to 400°C/2h together with frequency converter. However, we recommend bridging of frequency converter in case of fire to eliminate possible risk of malfunction of frequency converter. In case of fire all motor protective devices and thermal protections in frequency converter must be bridged or disabled to guarantee functional capability. When choosing AES control accessory please observe serial connecting capability of the motor (instructions).
Systemair BKF 560D4-6/F400
Модель: BKF
Артикул: 95715
Dual purpose fans: normal ventilation plus smoke and heat extract
• 400°C/120 min (F400)• Continuous operation up to 120°C media
• Casing made of zinc-magnesium coated steel (ZM)
• Backward curved impeller made from pre-galvanized steel or from steel and galvanized
• Motor outside the air stream
• Single speed IE2 motors (IE1 exceptions at some items up to 0,55 kW and 8 pole) rsp. two speed motors
• PTC serial built-in motor
• Certified according EN 12101-3 by BSI
• Installation possible in all positions, flange connection 30 mm
• Installation outside building or inside building, outside fire zone in well ventilated rooms
BKF smoke and heat extract fans are used in case of fire to extract smoke gases and also during normal working conditions for standard ventilation.
Smoke free escape routes assist egress and provide clear access points for fire departments. Extracting poisonous and hot gases also make fire extinguishing easier and reduce the damage on the building.
Applications: malls, garages, warehouses, kitchen exhaust...
Generally suitable for ambient temperature -20 to +40°C (depending on specific motor load the permissible ambient temperature may be increased - on request)
For speed control of single speed motors use combination of frequency converter and appropriate filter to motor side (sine or du/dt), respectively observe instructions. Not suitable for voltage control. Working points within blue area of diagrams of single speed fans can be achieved with frequency converter. Tested to 400°C/2h together with frequency converter. However, we recommend bridging of frequency converter in case of fire to eliminate possible risk of malfunction of frequency converter. In case of fire all motor protective devices and thermal protections in frequency converter must be bridged or disabled to guarantee functional capability. When choosing AES control accessory please observe serial connecting capability of the motor (instructions).
Systemair BKF 560D4-8/F400
Модель: BKF
Артикул: 95716
Dual purpose fans: normal ventilation plus smoke and heat extract
• 400°C/120 min (F400)• Continuous operation up to 120°C media
• Casing made of zinc-magnesium coated steel (ZM)
• Backward curved impeller made from pre-galvanized steel or from steel and galvanized
• Motor outside the air stream
• Single speed IE2 motors (IE1 exceptions at some items up to 0,55 kW and 8 pole) rsp. two speed motors
• PTC serial built-in motor
• Certified according EN 12101-3 by BSI
• Installation possible in all positions, flange connection 30 mm
• Installation outside building or inside building, outside fire zone in well ventilated rooms
BKF smoke and heat extract fans are used in case of fire to extract smoke gases and also during normal working conditions for standard ventilation.
Smoke free escape routes assist egress and provide clear access points for fire departments. Extracting poisonous and hot gases also make fire extinguishing easier and reduce the damage on the building.
Applications: malls, garages, warehouses, kitchen exhaust...
Generally suitable for ambient temperature -20 to +40°C (depending on specific motor load the permissible ambient temperature may be increased - on request)
For speed control of single speed motors use combination of frequency converter and appropriate filter to motor side (sine or du/dt), respectively observe instructions. Not suitable for voltage control. Working points within blue area of diagrams of single speed fans can be achieved with frequency converter. Tested to 400°C/2h together with frequency converter. However, we recommend bridging of frequency converter in case of fire to eliminate possible risk of malfunction of frequency converter. In case of fire all motor protective devices and thermal protections in frequency converter must be bridged or disabled to guarantee functional capability. When choosing AES control accessory please observe serial connecting capability of the motor (instructions).
Systemair BKF 630D4-6-XL/F400
Модель: BKF
Артикул: 95727
Dual purpose fans: normal ventilation plus smoke and heat extract
• 400°C/120 min (F400)• Continuous operation up to 120°C media
• Casing made of zinc-magnesium coated steel (ZM)
• Backward curved impeller made from pre-galvanized steel or from steel and galvanized
• Motor outside the air stream
• Single speed IE2 motors (IE1 exceptions at some items up to 0,55 kW and 8 pole) rsp. two speed motors
• PTC serial built-in motor
• Certified according EN 12101-3 by BSI
• Installation possible in all positions, flange connection 30 mm
• Installation outside building or inside building, outside fire zone in well ventilated rooms
BKF smoke and heat extract fans are used in case of fire to extract smoke gases and also during normal working conditions for standard ventilation.
Smoke free escape routes assist egress and provide clear access points for fire departments. Extracting poisonous and hot gases also make fire extinguishing easier and reduce the damage on the building.
Applications: malls, garages, warehouses, kitchen exhaust...
Generally suitable for ambient temperature -20 to +40°C (depending on specific motor load the permissible ambient temperature may be increased - on request)
For speed control of single speed motors use combination of frequency converter and appropriate filter to motor side (sine or du/dt), respectively observe instructions. Not suitable for voltage control. Working points within blue area of diagrams of single speed fans can be achieved with frequency converter. Tested to 400°C/2h together with frequency converter. However, we recommend bridging of frequency converter in case of fire to eliminate possible risk of malfunction of frequency converter. In case of fire all motor protective devices and thermal protections in frequency converter must be bridged or disabled to guarantee functional capability. When choosing AES control accessory please observe serial connecting capability of the motor (instructions).